apcupsd-ups (8) - Linux Manuals
apcupsd-ups: Driver for apcupsd client access
NAME
apcupsd-ups - Driver for apcupsd client access
NOTE
This man page only documents the specific features of the apcupsd-ups driver. For information about the core driver, see nutupsdrv(8).
DESCRIPTION
This driver is a client to apcupsd.
apcupsd-ups acts as an apcupsd client, simply forwarding data. This can be useful in cases where both protocols are required in a network, or in case apcupsd has a required UPS access mode missing from NUT.
EXTRA ARGUMENTS
This driver supports the following optional settings in nut.conf(5):
port=<hostname>[:<port>]
- This is the name of a remote host running apcupsd (plus an optional port).
For instance:
-
[apcupsd] driver = apcupsd-ups port = localhost desc = "apcupsd client"
BACKGROUND
This driver was originally written in one evening to allow interworking with apcupsd.
SUPPORTED VARIABLES
The following variables are translated from apcupsd to NUT. All times should be converted to seconds (please file a bug if you notice a mismatch in units).
apcupsd variable |
NUT variable(s)
|
BCHARGE |
battery.charge
|
MBATTCHG |
battery.charge.low
|
RETPCT |
battery.charge.restart
|
BATTDATE |
battery.date
|
TIMELEFT |
battery.runtime
|
MINTIMEL |
battery.runtime.low
|
BATTV |
battery.voltage
|
NOMBATTV |
battery.voltage.nominal
|
LINEFREQ |
input.frequency
|
SENSE |
input.sensitivity
|
HITRANS |
input.transfer.high
|
LOTRANS |
input.transfer.low
|
LASTXFER |
input.transfer.reason
|
LINEV |
input.voltage
|
MAXLINEV |
input.voltage.maximum
|
MINLINEV |
input.voltage.minimum
|
NOMINV |
input.voltage.nominal
|
LINEFREQ |
output.frequency
|
OUTPUTV |
output.voltage
|
NOMOUTV |
output.voltage.nominal
|
DATE |
ups.date, ups.time
|
DSHUTD |
ups.delay.shutdown
|
DWAKE |
ups.delay.start
|
FIRMWARE |
ups.firmware, ups.firmware.aux
|
UPSNAME |
ups.id
|
LOADPCT |
ups.load
|
MANDATE |
ups.mfr.date
|
NOMPOWER |
ups.realpower.nominal
|
SERIALNO |
ups.serial
|
STATUS |
ups.status
|
ITEMP |
ups.temperature
|
STESTI |
ups.test.interval
|
SELFTEST |
ups.test.result
|
LIMITATIONS
Access to apcupsd is strictly read only: no commands can be issued. This stems from the design of apcupsd, where the settings are changed in apctest. In order to run apctest, apcupsd must be stopped (and apcupsd exposes the UPS to the network).
AUTHOR
SEE ALSO
Internet Resources:
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
The apcupsd home page: http://www.apcupsd.org/